Ayuda
Ir al contenido

Dialnet


Description of power lines by equivalent source system

    1. [1] Polytechnic University of Turin

      Polytechnic University of Turin

      Torino, Italia

  • Localización: Compel: International journal for computation and mathematics in electrical and electronic engineering, ISSN 0332-1649, Vol. 24, Nº 3, 2005, págs. 893-905
  • Idioma: inglés
  • Enlaces
  • Resumen
    • Purpose – The definition of a simple model of low frequency magnetic field created by power industrial installations can be approached by using an equivalent source system (ESS). Given a set of measured magnetic field points, the ESS, made by a limited set of current carrying wires or turns, must be placed and supplied in order to fit the measured magnetic field values. An optimisation procedure can be used to define the current values and the location of the ESS which minimize the error between the measured and computed magnetic field values.

      Design/methodology/approach – A two‐step optimal procedure is defined: in the outer step a stochastic optimisation routine is used to drive the geometric control parameters of the ESS while, in the inner step, the current values flowing through the sources are computed to find the minimization of the error with respect to a set of measured magnetic field values. The optimisation procedure is based on an artificial immune system algorithm which focuses on a deep exploration of the search space and gave interesting results both in terms of accuracy and computational efficiency.

      Findings – The results show that the proposed approach is able to reconstruct the magnetic field created by complex source system and give some accuracy measure on the reconstruction error. The optimisation process carried out also on conductor positions has allowed to find out the location of the real sources in an accurate way, also in presence of measurement errors.

      Originality/value – The approach proposed uses optimisation procedures to solve the inverse problem of source reconstruction starting by a set of measured magnetic field values. The definition of a simple equivalent source structure, together with an optimisation procedure to set its control parameters, allows to simulate complex magnetic field sources, like power substations or cable systems, in a very efficient and compact way.


Fundación Dialnet

Dialnet Plus

  • Más información sobre Dialnet Plus

Opciones de compartir

Opciones de entorno